Product Descriptions
1. Applications: It is applied to power plant, substation as a relay protection, breaker control, emergency lighting power supply and battery charger.
2. Specifications: a) Supply voltage : 380VAC± 15%(3 phases) b) Output rated voltage DC: 24V, 48V, 60V, 110V, 220V, 320V. c) Output current DC: 25A ~ 1000A d) Battery capacity: 7Ah~3000Ah e) DC voltage accuracy : -0.5%~+0.5% f) DC current accuracy: -0.5%~+0.5% g) Ripple factor: <0.5% h) Noise: <60dB i) Cabinet Dimensions(mm): W800xD600xH2260 ( W600\1000\1200 as options) j) Protection grade: IP21, IP31 (Others available) k) Environmental limits Ambient temperature: Storage: -40...+70°C Operation: -15...+45°C, no frost allowed Relative humidity: < 90%, no condensation allowed. Altitude: 0...1000 m without derating; 1000...4000 m with
derating.
3. Features: a) Charger: ABB Thyristor Power Converter, software Smart-Charger -2000 inside , with reversed discharging function for batteries b) Intelligentized central monitor ( include insulation, battery monitoring) c) High reliability,long life, maintenance-free
4. System Configuration: a) Charger: DCS800, ABB Thyristor Power Converter (German ABB original). b) Storage battery: sealed lead-acid battery, lead-acid battery, nickel-cadmium battery, etc. c) DC feeder: DC circuit breaker (ABB, Siemens, etc). d) Central monitor: Siemens or Mitsubishi PLC, color LCD human- machine interface, monitoring devices for battery and insulation.
No. |
Item |
DCB50*-*-24 |
DCB50*-*-48 |
DCB50*-*-60 |
DCB50*-*-110 |
DCB50*-*-220 |
DCB50*-*-320 |
1 |
Input AC Voltage(V) |
380V (±15%) |
2 |
Output DC Rated Voltage(V) |
24 |
48 |
60 |
110 |
220 |
320 |
3 |
Rectifier Rated Current(A) |
25,50,75,100,140,200,250,350,450,520,680,820,1000 |
4 |
Battery Capacity(Ah)
(Lead-acid battery C10 ) |
7,24,38,65,100,200,300,400,500,600,800,1000,2000,3000 |
5 |
Impulse current |
Lead-acid battery |
1-3C10 |
Alkaline Battery |
3-12C5 |
6 |
Stabilized voltage precision |
<±0.5% |
7 |
Stabilized current precision |
<±0.5% |
8 |
Ripple factor |
<0.5% |
9 |
Noise |
<60dB |
10 |
Battery monitor |
18, 36, 108 , 216 batteries |
11 |
Insulation inspection |
32,64,96,128,256 , 512 loops | |